AWG 14, 10 A, 5 m, 12 V
- Input
- AWG 14, 10 A, 5 m, 12 V → ΔV
- Expected output
- 0.83 V (6.89 %)
2 × 10 × 5 × 0.0172 ÷ 2.081.
voltage drop 24v 10 meters 14 awg
The tool opens in DC with AWG 14. Pick the AWG gauge, the voltage and the length: the conversion to mm² appears beside it, and the table compares AWG 24 to 4/0.
2 × 10 × 5 × 0.0172 ÷ 2.081.
2 × 8 × 10 × 0.0172 ÷ 2.081.
2 × 8 × 10 × 0.0172 ÷ 5.261.
2 × 5 × 3 × 0.0172 ÷ 0.823.
2 × 10 × 5 × 0.0172 ÷ (0.03 × 12).
2 × 8 × 10 × 0.0172 ÷ (0.03 × 24).
In DC or single-phase, ΔV = 2 × L × I × ρ ÷ S, with L in meters, I in amps, ρ in Ω·mm²/m and S in mm². For copper at 20 °C, 20 m, 25 A and 6 mm²: 2 × 20 × 25 × 0.0172 ÷ 6 = 2.87 V. At 220 V that is 1.30 %.
d = 0.127 × 92^((36 − n) ÷ 39) mm and area = π ÷ 4 × d². AWG 14 is 2.08 mm² and AWG 10 is 5.26 mm².
It depends on the device and the design. Since 1 V is already 8.3 % of 12 V, many people adopt tighter limits at low voltage; the limit is your own field in the tool.
Wire resistance creates a voltage drop and dissipates 2 × I² × R as heat. More length or less cross-section increases both.
Length is the one-way distance from the source to the load. The return path is already in the math.
Resistivity used: 0.0172 Ω·mm²/m.
Resistivity at 20 °C: annealed copper 1.72e-8 Ω·m (0.0172 Ω·mm²/m) and aluminum 2.82e-8 Ω·m (0.0282 Ω·mm²/m), temperature coefficients 0.00393 and 0.0039 per kelvin (Wikipedia, Electrical resistivity and conductivity).
| mm² | ΔV (V) | ΔV (%) | Voltage at the load | Cable loss | Meets |
|---|---|---|---|---|---|
| 34.4 | 15.64 | 185.6 | 860 | ✗ | |
| 22.93 | 10.42 | 197.1 | 573.3 | ✗ | |
| 17.2 | 7.818 | 202.8 | 430 | ✗ | |
| 11.47 | 5.212 | 208.5 | 286.7 | ✗ | |
| 6.88 | 3.127 | 213.1 | 172 | ✓ | |
| 4.3 | 1.955 | 215.7 | 107.5 | ✓ | |
| 2.867 | 1.303 | 217.1 | 71.67 | ✓ | |
| 1.72 | 0.7818 | 218.3 | 43 | ✓ | |
| 1.075 | 0.4886 | 218.9 | 26.87 | ✓ | |
| 0.688 | 0.3127 | 219.3 | 17.2 | ✓ | |
| 0.4914 | 0.2234 | 219.5 | 12.29 | ✓ | |
| 0.344 | 0.1564 | 219.7 | 8.6 | ✓ | |
| 0.2457 | 0.1117 | 219.8 | 6.143 | ✓ | |
| 0.1811 | 0.0823 | 219.8 | 4.526 | ✓ | |
| 0.1433 | 0.06515 | 219.9 | 3.583 | ✓ | |
| 0.1147 | 0.05212 | 219.9 | 2.867 | ✓ | |
| 0.09297 | 0.04226 | 219.9 | 2.324 | ✓ | |
| 0.07167 | 0.03258 | 219.9 | 1.792 | ✓ | |
| 0.05733 | 0.02606 | 219.9 | 1.433 | ✓ |
Limit of this tool. It calculates only the voltage drop from conductor resistance. It does not check ampacity, heating, overcurrent protection or any code minimum size, and it does not size the cable. That depends on the design and belongs to a licensed professional following your local electrical code.