Watts, Amps and Volts Calculator (Ohm's Law, Single and Three-Phase)
Find how many amps an appliance draws, how many watts fit in a current, Ohm's law, kVA to kW and three-phase current, with the formula behind every result.
Power is voltage times current, and only a factor changes from one system to another.
In direct current, power is P = V × I and Ohm's law ties the four quantities together: V = I × R, P = I² × R and P = V² ÷ R. Given any two, algebra gives the other two, which is what the Ohm's law tab does. In alternating current the power factor cosφ enters, the fraction of apparent power S (in VA) that becomes useful work (real power P, in W): P = S × cosφ. In a single-phase system S = V × I, so the current is I = P ÷ (V × cosφ). A 5,500 W shower is a pure resistance (cosφ close to 1): it draws 25 A at 220 V and 43.3 A at 127 V. The power is the same, only the current changes, and it halves when the voltage doubles. In a balanced three-phase system, with the voltage measured LINE-TO-LINE, S = √3 × V × I and P = √3 × V × I × cosφ. The formula follows from P = 3 × V_ln × I × cosφ with V_ln = V ÷ √3, and the line-to-neutral relation (line-to-line = √3 × line-to-neutral) is the same one that turns 127 V into about 220 V and 220 V into about 380 V. For example, 10 kW at 380 V with cosφ 0.92 needs 10,000 ÷ (√3 × 380 × 0.92) = 16.5 A in each phase. In two-phase with neutral (the same load on each phase) the math uses a factor of 2 and the line-to-neutral voltage. Reactive power is Q = S × sinφ, measured in var: it does no work but circulates and occupies conductor capacity. That is why UPS units and transformers are rated in kVA, and the watts they deliver are kVA × 1,000 × cosφ. The appliance powers on this page are typical nameplate values, only to get started. The tool computes the load current and does not pick a breaker or a wire gauge.
How to use it
Pick the system, the voltage and what you already know.
In Watts, amps and kVA, choose single-phase, two-phase or three-phase, the voltage (120, 230, 400 V or any other) and the power factor (1 for resistive loads like heaters and ovens).
Say what you know: power in W or kW, current in A or apparent power in VA or kVA. Tap a typical appliance to fill in the power and check the formula behind each result.
In the Ohm's law tab, type any two of voltage, current, resistance and power. Copy the result or a link that carries the values.
Embed
Use this tool on your site
Paste the code into your HTML and the tool shows up on your page, without J-Kit's navigation and ads. It still runs in the browser of whoever visits your site.
<iframesrc="https://jkit.tools/embed/en-US/watts-amps-volts-calculator"width="100%"height="600"style="border:0"loading="lazy"title="Watts, Amps and Volts Calculator"></iframe><p style="font-size:12px;margin:6px 0 0">Tool by <a href="https://jkit.tools/en/tools/watts-amps-volts-calculator">J-Kit</a></p>
Cite
Cite or link to this tool
Using it in a paper, class or post? Copy the link or a ready-made reference. The access date is today's.
<a href="https://jkit.tools/en/tools/watts-amps-volts-calculator">Watts, Amps and Volts Calculator</a>
References
Sources and references for this tool
These references help contextualize formulas, standards, APIs and limitations used on this page. They do not replace professional validation when a result has legal, financial, medical or operational impact.
At 220 V, 25 A (5,500 ÷ 220). At 127 V, 43.3 A (5,500 ÷ 127). A heater element is a pure resistance, so the power factor is 1. That figure is the appliance current: it does not say which breaker or wire to use, which is a job for a licensed electrician.
Use the voltage that reaches the appliance: line-to-neutral (120 V) or across two lines (240 V). Line-to-line in a three-phase system, 120 V line-to-neutral becomes about 381.1 V.
What you already know
Typical nameplate powers, only as a starting point. Every model differs: the label on your appliance rules. Edit the value freely.
Current25AI = P ÷ (V × cosφ)
Real power5,500W5.5 kWP (informada)
Apparent power5,500VA5.5 kVAS = V × I
Reactive power0varQ = S × senφ
I = 5,500 ÷ (220 × 1) = 25 A
Running for 1 hour it uses 5.5 kWh.
Typical appliances table
Appliance
W
A @ 120 V
A @ 240 V
5500
45.83
22.92
7500
62.5
31.25
4500
37.5
18.75
1000
8.333
4.167
1300
10.83
5.417
1900
15.83
7.917
1400
11.67
5.833
1500
12.5
6.25
2000
16.67
8.333
1800
15
7.5
1200
10
5
200
1.667
0.8333
9
0.075
0.0375
Current of each appliance at 120 V and 240 V with cosφ 1 (the field above). Motors and compressors often have cosφ below 1: change the field to see the effect.
Limit of this tool. It shows the current and powers implied by the load you enter. It does not size a breaker or a cable: that depends on installation method, length, circuit grouping and temperature, and belongs to a licensed electrician or engineer following your local code.